                              | How  to protect electromagnetic flow meter in thunderstorm weather |  10-06-2020 When installing the electromagnetic flow  meter ,we must ensure that both ends of the electromagnetic flow meter sensor  are grounded.The grounding ring must be reliably  grounded. The electromagnetic flow meter can only be accurately measured with  good grounding protection. So that to ensure prevent lightning strikes in the  thunderstorm weather.
 1.The power supply is 220v  unidirectional alternating current. An air switch is installed in the  instrument box. The lighning arrester and the air switch are connected in  parallel .the wire comes out of the air witch and is connected to a three-item  socket.  2.The length of the signal cable  between the converter and the sensor cannot be greater than 50M,and the signal  cable must be sheathed with a galvanized tube. If the galvanized pipe is in the air ,the galvanized pipe  should be reliably grounded with a wire and the grounding resistance is less  than 10. 3.The length of the ground wire  of the arrester cannot exceed 1M,and the cross-sectional area is more than 6MM  square multi-strand copper core insulated wire. If there is no ground net nearby ,a simple ground net  should be made near the arrester. The method is as follows: use three flat  steel bars or angle bars with a length of 1.5M and arrange them into the ground  in a regular triangle arrangement. The flat steel bars are used to weld the  three flat bars together. Weld bolts at one corner, and then connect the  grounding wire of the arrester to install the panel on the ground plane of the  220VAC grounding wire.     KFKC INSTRUMENT CO.,LTD specializes in the production of electromagnetic flowmeter, vortex flow meter, turbine flow meter for many years,complete specifications, various  forms, can meet your different needs in different occasions. 
   |