How to protect electromagnetic flow meter in thunderstorm weather |
10-06-2020
When installing the electromagnetic flow meter ,we must ensure that both ends of the electromagnetic flow meter sensor are grounded.
The grounding ring must be reliably grounded. The electromagnetic flow meter can only be accurately measured with good grounding protection. So that to ensure prevent lightning strikes in the thunderstorm weather.
1.The power supply is 220v unidirectional alternating current. An air switch is installed in the instrument box.
The lighning arrester and the air switch are connected in parallel .the wire comes out of the air witch and is connected to a three-item socket.
2.The length of the signal cable between the converter and the sensor cannot be greater than 50M,and the signal cable must be sheathed with a galvanized tube. If the galvanized pipe is in the air ,the galvanized pipe should be reliably grounded with a wire and the grounding resistance is less than 10.
3.The length of the ground wire of the arrester cannot exceed 1M,and the cross-sectional area is more than 6MM square multi-strand copper core insulated wire.
If there is no ground net nearby ,a simple ground net should be made near the arrester. The method is as follows: use three flat steel bars or angle bars with a length of 1.5M and arrange them into the ground in a regular triangle arrangement. The flat steel bars are used to weld the three flat bars together. Weld bolts at one corner, and then connect the grounding wire of the arrester to install the panel on the ground plane of the 220VAC grounding wire.
KFKC INSTRUMENT CO.,LTD specializes in the production of electromagnetic flowmeter, vortex flow meter, turbine flow meter for many years,complete specifications, various forms, can meet your different needs in different occasions.
|